quit

Get Free Quote

quit
Loading
Call Us: +91-9099966039 | Email: info@neskeb.com
Conductor

Bare Copper Wire IS: 8130


Insulation

HR/FR/FRLS-H/ZHFR Insulation compound with a high insulation resistance value

Color

Red, Green/Yellow, Blue, Black, Brown, Grey, Orange, White, Green, Yellow

IS

694 : 2010 & BS 6004


Special heat resistant insulation Higher current carrying capacity. Fine copper wires Highly thermal stable insulation
Excellent resistant to moisture, abrasion, grace, oil Long Life Excellent mechanical & electrical properties Standard Packing : Coils 90 and 180 m

Neskeb - FLEXIBLE CABLES (IS:694)
Size of Wire No. of Wire / Size of Wire insulation Thickness OD Max conductor resistance at 20°C Current rating
sqmm mm Mm mm Ω/km Amps
0.5 16/0.2 0.6 2.6 39 6
0.75 24/0.2 0.6 2.8 26 9
1.0 32/0.2 0.6 3.0 19.5 14
1.5 30/0.25 0.6 3.8 13.3 18
2.5 50/0.25 0.7 4.0 7.98 24
4.0 56/0.3 0.8 4.8 4.95 32
6.0 84/0.3 0.8 6.4 3.3 42
10.0 140/0.3 1.0 8.0 1.91 55
16.0 224/0.3 1.0 9.6 1.21 75
25.0 350/0.3 1.2 11.5 0.78 100
35.0 490/0.3 1.2 13.0 0.554 125
50.0 703/0.3 1.4 15.0 0.386 165
70.0 988/0.3 1.4 15.0 0.272 240
95.0 1349/0.3 1.6 17.5 0.206 300
120.0 608/0.5 1.6 19.0 0.161 325
150.0 767/0.5 1.8 21.0 0.129 352
185.0 943/0.5 2.0 23.5 0.106 400
240.0 1223/0.5 2.2 26.5 0.0801 475
300.0 1528/0.5 2.4 29.5 0.0641 550
400.0 2035/0.5 2.6 33.5 0.0486 670
500.0 2553/0.5 2.8 37.5 0.0384 750
630.0 3219/0.5 2.8 42.0 0.0287 875

* All are class 5 conductor

* HR/FR/FRLS-H/HFFR insulation is also available as per customer requirements

Fixed installation in conduits and under plaster, for appliance wiring and distribution stations.

Flexible Cables
Flexible Cables
Flexible Cables