Conductor

Bare Bunch Copper IS:8130

Insulation

PVC As Per IS:5831

Outer Sheath

PVC As Per IS:5831

Cable Standard

BS 6500, IS 694:2010

High Flexibility & Long Life Excellent resistant to moisture, abrasion, grace, oil Excellent mechanical & electrical properties
Standard Packing : Coils 100, 200,300, 500, 1000m Core Colour As per IS: 694:2010 : Red, Yellow, Blue Core Colour As per IEC:60227 : Black, Blue, Brown

Operating Temp

-10°c to max.+90°C

Nominal voltage

1.1 KV

Test voltage

3.0 KV

Min. bending radius

6 x cable diameter

Conductor Insulation Total Thickness of Double Sheath Conductor Resistance at 20°C (max) Current Rating at 40°C
Size of Cable No. of Wire / Size of Wire Thickness Core OD Thickness Overall Size    
Thickness Width    
Sq. mm. Nos./mm mm mm mm mm mm Ω/km Amps.
1.5 22/0.30 0.8 3.25 1.15 6.0 12.8 12.1 14
2.5 36/0.30 0.9 3.84 1.15 6.4 14.6 7.41 18
4.0 56/0.30 1.0 4.5 1.15 7.4 16.8 4.95 26
6.0 84/0.30 1.0 5.3 1.15 7.9 18.7 3.30 31
10.0 140/0.30 1.0 6.5 1.4 9.9 23.7 1.91 42
16.0 224/0.30 10. 8.0 1.4 11.4 28.0 1.21 57
25.0 350/0.30 1.2 10.1 2.0 14.7 35.5 0.780 72
35.0 490/0.30 1.2 11.3 2.0 16.2 39.5 0.554 90
50.0 703/0.30 1.4 13.6 2.2 18.3 45.5 0.386 115
70.0 988/0.30 1.4 15.3 2.2 20.0 51.0 0.272 143
95.0 1349/0.30 1.6 18.0 2.4 23.5 60.0 0.206 165

The number of wires is approximate and wire diameter is nominal; they shall be such as to satisfy the requirements of conductor resistance as per Class 5 of IEC 60228 / DIN VDE 0295 / IS 8130 / BS 6360



As Per IS:694:2010
Conductor Insulation Sheath Current Rating at 40°C
Size of Cable No. of Wire / Size of Wire Thickness Thickness Overall Size  
Thickness Width  
Sq. mm. Nos./mm mm mm mm mm Amps.
1.5 22/0.30 0.6 0.9 5.2 11.3 14
2.5 36/0.30 0.7 1.0 6.2 13.3 18
4.0 56/0.30 0.8 1.0 7.0 15.6 26
6.0 84/0.30 0.8 1.1 7.4 17.7 31

The number of wires is approximate and wire diameter is nominal.

They shall be so as to satisfy the requirements of conductor resistance as per

The number of wires is approximate and wire diameter is nominal.

They shall be so as to satisfy the requirements of conductor resistance as per

Ideal For Irrigation Pumps, Drinking Water Supply Pumps & Submersible Motor Power Supply.

Irrigation Pumps
Drinking Water Supply Pumps
Submersible Motor Power Supply